İçereği Atla

[140G-H2F3-D10] 140G 125A H Frame Molded Case Ckt-Bkr

[140G-H2F3-D10]Kalıplı Kasa Ckt-Bkr, 125A H Çerçeve, 480V'da 25 kA, T/M - Adjst Thrm / Adjst Mgntc, 3 Kutuplu, 100A, Yüzde 80 MCCB, Bara Montajı Yok, YOK, YOK, YOK

Brand: Allen Bradley

Product Code: 140G-H2F3-D10

https://erp.patrion.net/web/image/product.template/1154/image_1920?unique=9351403

    Bu kombinasyon mevcut değil.

    About the Product

    Technical Info
    Additional Info
    Number of poles 3
    With integrated under voltage release False
    Integrated earth fault protection False
    Complete device with protection unit True
    Rated permanent current Iu 100 A
    Type of control element Toggle
    Rated impulse withstand voltage (Uimp) 8 kV
    Frame size 125 A
    Magnetic trip current (Im) 500 to 1000 A
    Thermal trip current (Ir) 70 to 100 A
    Voltage for reverse-fed circuit breaker, max 480V AC per UL/CSA
    Watt loss Thermal magnetic type: 24.3 W
    Insulation voltage (Ui) Rated 1000V per IEC
    Thermal trip rating, max 93 A @ ambient temperature 50 °C
    Electrical life cycle 8000 @ 415V AC
    Interrupting rating 65kA @ 240V AC, 50/60 Hz per NEMA, UL, CSA
    Rated ultimate short-circuit breaking capacity (Icu) IEC 60947-2: 65kA @ 220...230V AC, 50/60 Hz
    Rated service short-circuit breaking capacity (Ics) IEC 60947-2: 100% lcu @ 500V DC, 3-poles in series, thermal-magnetic trip unit only
    Protection type T/M-adjustable thermal/adjustable magnetic TMA
    Motor drive integrated False
    With switched-off indicator False
    Motor drive optional True
    Position of connection for main current circuit Front side
    Type of electrical connection of main circuit Screw connection