Skip to Content

[140MP-A3E-C16] Motor Protection Circuit Breaker

[140MP-A3E-C16]Motor Koruma Devre Kesicisi, A Çerçeve, 10-16 A, Açma Sınıfı 10A, Standart Kesme Kapasitesi, Standart Manyetik Açma (15 x le'de Sabit)

Brand: Allen Bradley

Product Code: 140MP-A3E-C16

https://erp.patrion.net/web/image/product.template/76/image_1920?unique=3b47a4b

    This combination does not exist.

    About the Product

    Motor Protection Circuit Breaker, motorları aşırı akım, kısa devre ve faz hatalarına karşı etkili şekilde koruyan kompakt bir devre kesicidir. Endüstriyel otomasyon sistemlerinde motorların güvenli çalışmasını sağlar ve arıza riskini en aza indirir. Kolay montaj ve yer tasarrufu sunan tasarımıyla panolarda fark yaratır. Güçlü koruma özellikleriyle sistem verimliliğini artırır.

    Technical Info
    Additional Info
    With integrated under voltage release False
    Rated operating voltage 0 A
    Type of control element Turn button
    Type of electrical connection of main circuit Screw connection
    Rated impulse withstand voltage (Uimp) 6 kV
    Magnetic trip current 240 A
    Short circuit current for group motor, max 18kA @ 480V
    Motor current adjustment range 10...16 A
    Short circuit current Icu, max 15kA @ 400V
    Rated operational current (Ie) 16 A
    Ultimate short circuit breaking capacity (Icu) per IEC 6kA @ 500V AC
    Rated service short circuit breaking capacity (Ics) per IEC 4kA @ 500V AC
    Insulation voltage (Ui) Rated 690V
    Hp rating, max 5Hp @ 230V, 3-phase
    KW rating, max AC-3: 7.5 kW @ 400...415V, 3-phase
    Short circuit current rating Type 1 coordination: 5kA @ 600V AC
    Back up fuse (gG, gL) current rating (if Icc ≥ Icu ) per IEC 80A @ 400V
    Branch circuit protection per NEC/CEC, max UL 60947 manual motor controller: 175 A
    Trip class 10 A
    Fuse or circuit breaker size per NEC, max UL 60947-4-1 manual motor controller: 175 A
    Short circuit current, max Type 2 coordination, IEC 60947-4-1: 5kA @ 600V
    Fuse or circuit breaker per NEC, max UL 60947-4-1 manual motor controller: 175 A
    Short circuit current for group motor installation, max UL 60947 manual motor controller: 5kA @ 600V
    Short circuit current for motor disconnect, max UL 60947 manual motor controller: 5kA @ 600V
    Number of poles 3
    With thermal protection True
    Phase failure sensitive True
    Max current Ie 32 A
    Maximum operating voltage (UL) 600 V
    Disconnect function per IEC/EN 60947-2 True
    Rated operating voltage (Ue) 690V AC
    Rated frequency 50/60 Hz
    Number of operations Mechanical: 100.000 cycles, Electrical: 100000 cycles (0.1...16 A), 50000 cycles (20...32 A)
    Power loss 5.1 W @ 0.16...1.6 rated operating current, 5.4 @ 2.5...6.3 rated operating current, 7.2 @ 10...12 rated operating current, 8.4 @ 16...25 rated operating current, 9.3 @ 32 rated operating current