[140MP-A3E-B16] Motor Protection Circuit Breaker
[140MP-A3E-B16]Motor Koruma Devre Kesicisi, A Çerçeve, 1,0-1,6 A, Açma Sınıfı 10A, Standart Kesme Kapasitesi, Standart Manyetik Açma (12,5 x le'de Sabit)
Brand: Allen Bradley
Serial Number: 140MP-A3E-B16
About the Product
Technical and Additional Information
Technical Specifications
With integrated under voltage release: | False |
Rated operating voltage: | 0 A |
Type of control element: | Turn button |
Type of electrical connection of main circuit: | Screw connection |
Rated impulse withstand voltage (Uimp): | 6 kV |
Magnetic trip current: | 20 A |
Short circuit current for group motor, max: | 30kA @ 480V |
Motor current adjustment range: | 1.0...1.6 A |
Short circuit current Icu, max: | 100kA @ 400V |
Rated operational current (Ie): | 1.6 A |
Ultimate short circuit breaking capacity (Icu) per IEC: | 100kA @ 690V AC |
Rated service short circuit breaking capacity (Ics) per IEC: | 50kA @ 400V AC |
Insulation voltage (Ui): | Rated 690V |
Hp rating, max: | 1Hp @ 575V, 3-phase |
KW rating, max: | AC-3: 1.1 kW @ 690V, 3-phase |
Short circuit current rating: | Type 1 coordination: 5kA @ 600V AC |
Branch circuit protection per NEC/CEC, max: | UL 60947 manual motor controller: 175 A |
Trip class: | 10 A |
Fuse or circuit breaker size per NEC, max: | UL 60947-4-1 manual motor controller: 175 A |
Short circuit current, max: | Type 2 coordination, IEC 60947-4-1: 50kA @ 400V |
Fuse or circuit breaker per NEC, max: | UL 60947-4-1 manual motor controller: 175 A |
Short circuit current for group motor installation, max: | UL 60947 manual motor controller: 5kA @ 600V |
Short circuit current for motor disconnect, max: | UL 60947 manual motor controller: 5kA @ 600V |
Number of poles: | 3 |
With thermal protection: | True |
Phase failure sensitive: | True |
Max current Ie: | 32 A |
Maximum operating voltage (UL): | 600 V |
Disconnect function per IEC/EN 60947-2: | True |
Rated operating voltage (Ue): | 690V AC |
Rated frequency: | 50/60 Hz |
Number of operations: | Mechanical: 100.000 cycles, Electrical: 100000 cycles (0.1...16 A), 50000 cycles (20...32 A) |
Power loss: | 5.1 W @ 0.16...1.6 rated operating current, 5.4 @ 2.5...6.3 rated operating current, 7.2 @ 10...12 rated operating current, 8.4 @ 16...25 rated operating current, 9.3 @ 32 rated operating current |