İçereği Atla

[140MP-A3E-C12] Motor Protection Circuit Breaker

[140MP-A3E-C12]140MP Motor Koruma Devre Kesici / Manuel Motor Yolverici, Çerçeve Boyutu A, 3 kA, Ayarlanabilir Termal/Sabit Manyetik MPCB, 8,0 - 12,0A

Brand: Allen Bradley

Serial Number: 140MP-A3E-C12

https://erp.patrion.net/web/image/product.template/536/image_1920?unique=4ee4e6d

    Bu kombinasyon mevcut değil.

    About the Product

    Technical and Additional Information
    Technical Specifications
    With integrated under voltage release: False
    Rated operating voltage: 0 A
    Type of control element: Turn button
    Type of electrical connection of main circuit: Screw connection
    Rated impulse withstand voltage (Uimp): 6 kV
    Magnetic trip current: 180 A
    Short circuit current for group motor, max: 18kA @ 480V
    Motor current adjustment range: 8.0...12 A
    Short circuit current Icu, max: 50kA @ 400V
    Rated operational current (Ie): 12 A
    Ultimate short circuit breaking capacity (Icu) per IEC: 50kA @ 400V AC
    Rated service short circuit breaking capacity (Ics) per IEC: 6kA @ 500V AC
    Insulation voltage (Ui): Rated 690V
    Hp rating, max: 7.5Hp @ 460V, 3-phase
    KW rating, max: AC-3: 7.5 kW @ 690V, 3-phase
    Short circuit current rating: Type 1 coordination: 5kA @ 600V AC
    Back up fuse (gG, gL) current rating (if Icc ≥ Icu ) per IEC: 80A @ 400V
    Branch circuit protection per NEC/CEC, max: UL 60947 manual motor controller: 175 A
    Trip class: 10 A
    Fuse or circuit breaker size per NEC, max: UL 60947-4-1 manual motor controller: 175 A
    Short circuit current, max: Type 2 coordination, IEC 60947-4-1: 5kA @ 600V
    Fuse or circuit breaker per NEC, max: UL 60947-4-1 manual motor controller: 175 A
    Short circuit current for group motor installation, max: UL 60947 manual motor controller: 5kA @ 600V
    Short circuit current for motor disconnect, max: UL 60947 manual motor controller: 5kA @ 600V
    Number of poles: 3
    With thermal protection: True
    Phase failure sensitive: True
    Max current Ie: 32 A
    Maximum operating voltage (UL): 600 V
    Disconnect function per IEC/EN 60947-2: True
    Rated operating voltage (Ue): 690V AC
    Rated frequency: 50/60 Hz
    Number of operations: Mechanical: 100.000 cycles, Electrical: 100000 cycles (0.1...16 A), 50000 cycles (20...32 A)
    Power loss: 5.1 W @ 0.16...1.6 rated operating current, 5.4 @ 2.5...6.3 rated operating current, 7.2 @ 10...12 rated operating current, 8.4 @ 16...25 rated operating current, 9.3 @ 32 rated operating current