Skip to Content

[140MP-A3E-B40] Motor Protection Circuit Breaker

[140MP-A3E-B40]Motor Koruma Devre Kesicisi, A Çerçeve, 2,5-4,0 A, Açma Sınıfı 10A, Standart Kesme Kapasitesi, Standart Manyetik Açma (12,5 x le'de Sabit)

Brand: Allen Bradley

Product Code: 140MP-A3E-B40

https://erp.patrion.net/web/image/product.template/73/image_1920?unique=9351403

    This combination does not exist.

    About the Product

    Technical Info
    Additional Info
    With integrated under voltage release False
    Rated operating voltage 0 A
    Type of control element Turn button
    Type of electrical connection of main circuit Screw connection
    Rated impulse withstand voltage (Uimp) 6 kV
    Magnetic trip current 50 A
    Short circuit current for group motor, max 18kA @ 480V
    Motor current adjustment range 2.5...4 A
    Short circuit current Icu, max 75kA @ 400V
    Rated operational current (Ie) 4 A
    Ultimate short circuit breaking capacity (Icu) per IEC 75kA @ 400V AC
    Rated service short circuit breaking capacity (Ics) per IEC 6kA @ 500V AC
    Insulation voltage (Ui) Rated 690V
    Hp rating, max 3Hp @ 575V, 3-phase
    KW rating, max AC-3: 3 kW @ 690V, 3-phase
    Short circuit current rating Type 1 coordination: 5kA @ 600V AC
    Back up fuse (gG, gL) current rating (if Icc ≥ Icu ) per IEC 25A @ 690V AC
    Branch circuit protection per NEC/CEC, max UL 60947 manual motor controller: 175 A
    Trip class 10 A
    Fuse or circuit breaker size per NEC, max UL 60947-4-1 manual motor controller: 175 A
    Short circuit current, max Type 2 coordination, IEC 60947-4-1: 50kA @ 400V
    Fuse or circuit breaker per NEC, max UL 60947-4-1 manual motor controller: 175 A
    Short circuit current for group motor installation, max UL 60947 manual motor controller: 5kA @ 600V
    Short circuit current for motor disconnect, max UL 60947 manual motor controller: 5kA @ 600V
    Number of poles 3
    With thermal protection True
    Phase failure sensitive True
    Max current Ie 32 A
    Maximum operating voltage (UL) 600 V
    Disconnect function per IEC/EN 60947-2 True
    Rated operating voltage (Ue) 690V AC
    Rated frequency 50/60 Hz
    Number of operations Mechanical: 100.000 cycles, Electrical: 100000 cycles (0.1...16 A), 50000 cycles (20...32 A)
    Power loss 5.1 W @ 0.16...1.6 rated operating current, 5.4 @ 2.5...6.3 rated operating current, 7.2 @ 10...12 rated operating current, 8.4 @ 16...25 rated operating current, 9.3 @ 32 rated operating current