[140G-H2F3-D12] 140G 125A H Frame Molded Case Ckt-Bkr
[140G-H2F3-D12]140G - Kompakt Devre Kesici, H çerçeve, 25 kA Kesme Değeri, T/M - Termal Manyetik, 3 Kutuplu, Nominal Akım 125 A
Brand: Allen Bradley
Serial Number: 140G-H2F3-D12
About the Product
Technical and Additional Information
Technical Specifications
Number of poles: | 3 |
With integrated under voltage release: | False |
Integrated earth fault protection: | False |
Complete device with protection unit: | True |
Rated permanent current Iu: | 125 A |
Type of control element: | Toggle |
Rated impulse withstand voltage (Uimp): | 8 kV |
Frame size: | 125 A |
Magnetic trip current (Im): | 625 to 1250 A |
Thermal trip current (Ir): | 87 to 125 A |
Voltage for reverse-fed circuit breaker, max: | 480V AC per UL/CSA |
Watt loss: | Thermal magnetic type: 34.2 W |
Insulation voltage (Ui): | Rated 1000V per IEC |
Thermal trip rating, max: | 125 A @ ambient temperature 40 °C |
Electrical life cycle: | 8000 @ 415V AC |
Interrupting rating: | 65kA @ 240V AC, 50/60 Hz per NEMA, UL, CSA |
Rated ultimate short-circuit breaking capacity (Icu): | IEC 60947-2: 65kA @ 220...230V AC, 50/60 Hz |
Rated service short-circuit breaking capacity (Ics): | IEC 60947-2: 100% lcu @ 500V DC, 3-poles in series, thermal-magnetic trip unit only |
Protection type: | T/M-adjustable thermal/adjustable magnetic TMA |
Motor drive integrated: | False |
With switched-off indicator: | False |
Motor drive optional: | True |
Position of connection for main current circuit: | Front side |
Type of electrical connection of main circuit: | Screw connection |